nut-dog

UPS-triggered graceful shutdown + load-shedding for the HLA1 rack. A stateless, level-triggered controller: every poll it reads both UPSes and the actual power state of each load, then drives the loads toward what the telemetry implies. No timers, no persisted state — a restart just re-reads the world and continues.

On a mains failure it sheds the blade chassis (BC1) and the Proxmox host (p1) early so the always-on networking tier rides the battery through short blips, then powers everything back when mains returns. See JHC-501 for the full design.

How it works

┌──────────────── nut-dog pod ────────────────┐
│  nut-dog   (the controller — decides)        │
│  upsd      (NUT server p1's upsmon talks to) │
│   ├─ snmp-ups  → reads UPS-A (CyberPower RMCARD, the grid sensor)
│   └─ dummy-ups → a "shed-<server>" signal per NUT server
└──────────────────────────────────────────────┘
  • UPS-A (RMCARD, SNMPv3) is the grid sensor and powers BC1. UPS-B (UniFi, NUT over TLS) powers the networking tier + p1. Both are polled for battery.runtime / battery.charge / ups.status.
  • A load sheds when any governing UPS is critical (on battery && runtime ≤ shedRuntime) and recovers only when all are healthy again (charge deadband prevents flapping).
  • BC1: racadm chassisaction powerdown / powerup over SSH to the CMC; blades self-boot on power-up via their iDRAC power-restore policy.
  • p1 (and any NUT server): shed over NUT — the controller flips its shed-<name> dummy-ups critical and its own upsmon shuts it down; woken via Wake-on-LAN. Adding a server is a config block, nothing else.

Sharing a load with another controller

energy-watchdog decides when p1 should be off for solar reasons, but nut-dog owns the power itself: it is the service that has to work during an outage, and its mechanisms (the shed signal, WoL) need neither Proxmox nor the cluster.

So energy-watchdog asks, over powerAPI:

PUT /api/loads/p1/power   {"desired": "on" | "off" | "hold", "reason": "..."}
GET /api/loads/p1/state   -> {"actual": "up" | "down" | "unknown", "ageSeconds": 3}
Authorization: Bearer <token>

The GET serves back what the last reconcile's probe saw. It exists because our probe answers a question the caller cannot answer for itself: it reaches the host directly, while energy-watchdog reads node state from the rest of the pve cluster, which reports a node partitioned from corosync exactly as it reports one that is switched off. Acting on that confusion shed a running host once. ageSeconds is computed here, so the caller needs no agreement with our clock to judge whether the reading is still worth anything.

A request never outranks a UPS event. DesiredForLoad resolves it: a critical source sheds the load regardless of who wants it on; below that, off is honoured in any state, and on only once every source is healthy — that rule is the whole wake interlock, and it needs no coordination with the caller.

hold is a request in its own right, not a withdrawal: it pins the load where it is, which is what stops nut-dog powering it back on by itself while the caller is mid-operation. That is deliberately different from no request at all, which hands the load back to the UPS verdict — and a healthy UPS means on. There is no way to return a load to "no request" by hand; requestTTL (default 10h) does it on its own once nobody has restated, and restarting nut-dog clears everything, since it keeps none of this.

Expiry is not a neutral state: it hands the load back to its UPSes, and healthy UPSes mean on. So a caller that dies eventually gets its load powered up rather than pinned where it left it — deliberate, since a stranded load is the harder failure to notice. energy-watchdog restates every tick even when it has lost Prometheus, so only a genuinely dead one trips it.

Requests live in memory only. Callers restate their wish every tick, so nothing has to survive a restart and no stale file can hold a load down. startupGrace covers the window after a restart where nut-dog hasn't been told yet: for that long it takes no power-on action. Sheds are never held — a restart must never delay an emergency.

powerAPI.loads is an allowlist. The token is authority over those loads only.

Config

Everything is config-driven — see config.example.yaml. The pod's NUT server config (ups.conf / upsd.users / shed signals) is generated from it, so adding a UPS or server never touches code or templates. Secret values come from the environment (referenced by *Env fields).

Develop

go test ./...                 # unit tests
go build ./cmd/nut-dog        # the controller
go build ./cmd/nut-probe      # dump a UPS's telemetry (validate a NUT/SNMP UPS)

# integration tests (need nut-server + nut-client, run as root):
sudo ./test/integration/shed_test.sh          # shed signal shuts a upsmon secondary
sudo ./test/integration/shed_failover_test.sh # ...and still does with a second, unreachable server
sudo ./test/integration/controller_e2e.sh     # real controller sheds/recovers multiple servers

Formatted with gofumpt. CI (.github/workflows/ci.yaml) runs the unit + integration + image-smoke tests, and on main uses semantic-release to version and push the multi-arch image to ghcr.io/jhofer-cloud/nut-dog.

Deploy

Deployed via GitOps from the fleet repo (infra/nut-dog/), pinned to an always-on control-plane Pi, hostNetwork, shipping dryRun: true until the live pull-the-plug drill passes.

Observability

Serves Prometheus metrics (nut_dog_*) and /healthz on :9334: per-UPS telemetry freshness (the fail-safe's key blind spot), the controller's decisions (desired/actual/shed per load), action failures, and the full UPS telemetry it polls (charge, runtime, load, voltages, temperature). Scrape config and alerts live in fleet (infra/nut-dog/common/serviceMonitor.yaml, infra/monitoring/.../nut-dog-alerts.yaml).

Grafana dashboard: fleet-dashboards → sync/K8s/Misc/nut-dog.json.